The 16A Series temperature / process controls set a new standard in 1/16 DIN power, flexibility, and value. This family of controls offers complete interchangability with different levels of features.
|
|
The 16A offers universal input (10 thermocouple types, 4 RTD types, voltage, and current), single or dual set point, alarm (optional), Fuzzy Logic, Self-tune, Peak / Valley indication, Percent Output indication, and Heater Break protection.
The 16A3 adds to this impressive list, Auto / Manual capability, and 16 Segment Ramp and Soak with adjustable time base.
Options for the 16A2 and 16A3 include Process Output Retransmission (Voltage or Current), Remote Analog Set Point (Voltage, Current, Resistance), RS-232 Serial Communiction, RS-485 Serial Communication, and 4-Stage Set Point.
Designed and built in the USA, the 16A family of controls offer the highest levels of features, function, and quality available today.


|
INPUT TYPE |
RANGE deg. F |
RANGE deg. C |
|
Type J or L (see note 1) |
-100 to +1607 |
-73 to +871 |
|
Type K (see note 1) |
-200 to +2500 |
-129 to +1371 |
|
Type T (see note 1) |
-350 to +750 |
-212 to +398 |
|
Type E (see note 1) |
-100 to +1800 |
-73 to +982 |
|
Type R |
0 to 3200 |
-17 to +1760 |
|
Type S |
0 to 3200 |
-17 to +1760 |
|
Type B |
+75 to +3308 |
+24 to +1820 |
|
Type C |
0 to +4208 |
-17 to +2320 |
|
Type N (see note 1) |
-100 to +2372 |
-73 to +1300 |
|
100 Ohm Platinum 0.00385 DIN (see note 1) |
-328 to +1607 |
-200 to +875 |
|
100 Ohm Platinum 0.00392 Nist (see note 1) |
-328 to +1607 |
-200 to +875 |
|
120 Ohm Nickel 0.00628 US (see note 1) |
-112 to +608 |
-80 to +320 |
|
1000 Ohm Platinum 0.00385 Nist (see note 1) |
-328 to +1607 |
-200 to +875 |
|
Current/Voltage/Differential Voltage (see note 2) |
Scalable Units from -1999 to +9999 |
|
Notes:
1. These Input Types can be set for 0.1 deg. display. If temperature goes above 999.9 deg. or less than -199.9 deg. the display will return to whole degree resolution.
2. The 0 to 20 mADC, 4 to 20 mADC, 0 to 10 VDC, 2 to 10 VDC, and -10 to +10 mVDC inputs are fully scalable from a minimum of 100 counts span placed anywhere within the range of -1999 to +9999. Decimal point position is adjustable from the zero place (9999), tenths (999.9), hundredths (99.99), thousanths (9.999), or ten thousandths (.9999).
|
Selectable Inputs: Input Impedance: Sensor Break Protection: Set Point Range: Display: Control Action: Proportional Band: Reset Time (Integral): Rate Time (Derivative): Cycle Rate: 1 to 80 seconds On - Off Differential: Alarm On - Off Differential: Fuzzy Intensity: 0 to 100% Fuzzy Rate: Fuzzy Band: Accuracy: Resolution: |
Line Voltage Stability: Temperature Stability: Isolation: Supply Voltage: Power Consumption: 5 VA maximum Operating Temperature: Storage Temperature: -40 to +80 deg. C (-40 to +176 deg. F) Humidity Conditions: Memory Backup: Control Output Ratings: DC SSR: 1.75 A @ 32 VDC maximum isolated. Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 250 VA, 2 A @ 120 VAC or 1 A @ 240 VAC. Alarm Relay: SPST, 3 A @ 240 VAC resistive; 1.5 A @ 240 VAC inductive; Pilot Duty Rating: 240 VA, 2 A @ 120 VAC or Current (isolated): 0 to 20 mA across 600 ohms maximum. Switched Voltage (isolated): 15 VDC @ 20 mA. Panel Cutout: 45 mm X 45 mm (1.775" X 1.775"). Depth Behind Mounting Surfaces: 115.3 mm (4.54"). Weight: 227 g (8 oz). Agency Approvals: UL E83725, CE. Front Panel Rating: Type 4X, (IP66). |
To order, specify part number by filling the boxes with the appropriate numbers. If no options are desired, leave those boxes blank.
|
|
Feature Set |
Alarm |
Output A (see note) |
Output B (see note) |
- Options |
|
16A |
2 = Standard |
0 = No |
1 = AC SSR |
0 = None |
See Options List |
Note:
When ordering a control to operate contactor or solenoid loads greater than 100 mA, it is suggested that the SSR output be selected rather than the RELAY. If the RELAY output is selected, then also order part number 541-0014, R/C Snubber.
|
924 |
Analog Remote Set Point, 0 to 10 VDC. |
|
926 |
Analog Remote Set Point, 4 to 20 mADC. |
|
928 |
Analog Remote Set Point, 0 to 10,000 ohms. |
|
934 |
Analog Retransmission of Process Variable or Set Variable, 4 to 20 mADC. |
|
936 |
Analog Retransmission of Process Variable or Set Variable, 0 to 10 VDC. |
|
948 |
4-Stage Set Point. One of four pre-set set point values can be implemented via contact closure. |
|
992 |
RS-485 Serial Communications. Allows remote computer to read and write all control parameters. |
|
993 |
RS-232 Serial Communications. Allows remote computer to read write all control parameters. |