LLC5 Series

  • Dual Probe Level Detection
  • Solid State Circuitry
  • Sense Resistance Factory Fixed or Adjustable
  • UL & CSA
  • Coated Circuitry for Moisture Protection
  • Electromechanical Relay Output for Isolation and Reliability

Description

The LLC5 Liquid Level Control provides high level, low level (bilevel) control in a convenient octal plug-in package. Models are available for pump-up (fill type) or pump-down (drain type) operation. Transformer isolated AC voltage on the probes prevents electrolytic plating. Less than 1/1000 of an amp of current is used to sense the presence of conductive liquid between the probes and common. Onboard sensitivity adjustment, on adjustable units, eliminates false tripping caused by floating debris and foaming agents. Isolated electromechanical relay contacts can be connected to the control circuitry or control pumps and solenoids directly.

SPECIFICATIONS

1. Control

1.1 Type: ON/OFF Resistance Sensing
1.2 Sense Voltage: 12 volts AC nominal at probe terminals
1.3 Sense Resistance: Factory fixed or adjustable to 100,000 ohms
1.4 Sense Resistance Tolerance: Adjustable: Guaranteed Range Factory Fixed: ±10%

2. Operating Voltage (Input)

2.1 Voltage: 24, 120, or 230 volts AC
2.2 Tolerance: ±15% nominal
2.3 Frequency: 50/60 Hertz

3. Output

3.1 Type: Electromechanical relay
3.2 Form: Single pole double throw isolated contacts
3.3 Rating: 5 amps resistive at 240VAC

4. Protection

4.1 Transient Protected
4.2 Dielectric Breakdown: 1500 volts RMS minimum

5. Mechanical

5.1 Mounting: Plug-in
5.2 Termination: Octal (8 Pin) Plug

6. Environment

6.1 Operating Temperatures: -20 deg. C to +60 deg. C
6.2 Storage Temperature: -40 deg. C to +80 deg. C

CONNECTION

OPERATION

MODE OF OPERATION A- Drain Type: As long as liquid does not come in contact with the upper probe, the relay contacts remain in an unenergized position. If liquid rises to the upper probe level, the relay contacts will transfer to the energized position, until the liquid drops below the lower probe level. When this occurs, the relay will immediately de-energize.

MODE OF OPERATION B- Fill Type: As long as liquid remains between the upper and lower probes, the relay contacts will remain in an unenergized position. If liquid drops below the lower probe, the control relay will be energized. The relay contacts will remain in the energized position until the level of the liquid reaches the upper probe. When this occurs, the relay immediately de-energizes.

MECHANICAL

ORDERING INFORMATION

Series

Operating Voltage

Logic Type

Sense Resistance

Connection

LLC5

2- 24VAC
4- 120VAC
6- 230VAC

A- Drain
B- Fill

A- Adjustable
F- Fixed (Specify fixed resistance in 1k ohm increments)
100k ohms maximum

Blank- Standard
(#6 Low, #8 High)

S- Reverse
(#8 Low, #6 High)

Example Part Number: LLC56BF100 is a dual probe level control with a 230VAC input, Fill type logic and a fixed sense resistance of 100k ohms. Add suffix S for reverse probe connections (Low #8, High #6).